Classification Basics

A Class I, Division 2 location is a location:

     (1) In which volatile flammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors are handled, processed, or used, but in which the liquids, vapors, or gases will normally be confined within closed containers or closed systems from which they can escape only in case of accidental rupture or breakdown of such containers or systems or in case of abnormal operation of equipment, or

     (2) In which ignitable concentrations of flammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors are normally prevented by positive mechanical ventilation, and which might become hazardous through failure or abnormal operation of the ventilating equipment, or

     (3) That is adjacent to a Class I, Division 1 location, and to which ignitable concentrations offlammable gases, flammable liquid-produced vapors, or combustible liquid-produced vapors might occasionally be communicated unless such communication is prevented by adequate positive-pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided.

        (FPN No. 1):  This classification usually includes locations where volatile flammable liquids or flammable gases or vapors are used but that, in the judgment of the authority having jurisdiction, would become hazardous only in case of an accident or of some unusual operating condition. The quantity of flammable material that might escape in case of accident, the adequacy of ventilating equipment, the total area involved, and the record of the industry or business with respect to explosions or fires are all factors that merit consideration in determining the classification and extent of each location.

        (FPN No. 2):  Piping without valves, checks, meters, and similar devices would not ordinarily introduce a hazardous condition even though used for flammable liquids or gases. Depending on factors such as the quantity and size of the containers and ventilation, locations used for the storage of flammable liquids or liquefied or compressed gases in sealed containers may be considered either hazardous (classified) or unclassified locations. See NFPA 30-2000, Flammable and Combustible Liquids Code, and NFPA 58-2001, Liquefied Petroleum Gas Code.
NOTE: This is an unformatted excerpt from our online fire protection training library.

Contact Us:

Please fill in the fields below:

    Privacy Policy
    Please choose all that interest you.

    Contact Customer Service at AcademySupport@jensenhughes.com or 800-930-9414 option 1.

    Our regular support hours are 9:00 AM to 5:00 PM, Monday through Friday, except holidays...