Zone Classification

Zone Wiring Methods

Zone 0

The only protection method permitted in Zone 0 areas is intrinsic safety. Article 505 refers to Article 504 for wiring methods for intrinsically safe circuits. Article 504 permits any of the wiring methods that are suitable for use in unclassified areas suitable for use in unclassified areas:
The wiring methods are subject to any occupancy or location restrictions that apply to that wiring method. For example, Type NM cable is not permitted in wet locations, and Type CL2 cable is not permitted to be exposed (without an enclosure) in a riser or in "other space for environmental air." to be used for intrinsically safe wiring and apparatus. This includes the wiring methods of Chapters 7 and 8 Chapters 7 and 8:
These include the special wiring methods for Class 2 and Class 3 circuits, fire alarm circuits (both power-limited and nonpower-limited) and communications cables.of the NEC. Intrinsically safe wiring must be separated from other wiring separated from other wiring:
These requirements are found in Section 504.30 of the NEC. and must be identified throughout the installation identified throughout the installation:
These requirements are found in Section 504.80 of the NEC. as required by Article 504.