Load Calculations

Branch Circuit Load Calculations

Subsection 210.14(K)

Notice that the value for office buildings refers to Subsection 220.14(K). This section applies to banks and office buildings where the building is often built without knowing who all the tenants are or what the final loads will be. This rule allows the use of 1 VA per square foot to calculate the receptacle loads in such a building when it is not actually known how many receptacles there are.