Remote Station and Protected Premises Fire Alarm Systems

Combination Systems

Wiring and Faults

If any wiring problems, such as short circuits or opens occur on the non-fire part of the combined system, the fire alarm system must still function properly.  Fire alarm signals can't be prevented, and all monitoring of the fire alarm system must remain intact.

If the removal, replacement, failure or maintenance procedure of a non-fire alarm component will cause a monitoring or signal transmission problem with the fire alarm system, the component and its wiring must be listedThis also means that the component, and its wiring will be required to be monitored for integrity by the fire alarm system, as all components listed for fire service will be monitored for integrity when installed in the fire alarm system. for fire alarm service.