Equipment Selection

Flexible Connections

Where flexible connections are needed, dusttight flexible connectors, liquidtight flexible metal conduit, liquidtight flexible nonmetallic conduit, or flexible cords may be used. Fittings used with flexible conduits must be listed. The flexible conduit may not be used as a grounding means. A bonding jumper may be installed on the outside of the conduit if the length does not exceed 6 feet.